Menu

Low-voltage complete devices SIVACON 8PT, SIVACON S8, SIEMENS.

The company "Servismontazhintegratsiya" produces low voltage switchboards SIVACON under the license issued by SIEMENS. The devices are used for receiving, control and distribution of electricity and are used to protect power grids with voltage up to 690 V with frequency of 50 Hz.

The series equipment SIVACON is a ready functional solution for low voltage distribution units, main and auxiliary distribution panels and master control panels with degree of protection up to IP 54. Used in installations of power plants and enterprises engaged in the transport, industrial and agricultural industries, as well as on the urban infrastructure (shopping malls, schools, hospitals, etc.).

OOO "Servismontazhintegratsiya" is the official partner of the SIEMENS company. We produce low voltage switchgear SIVACON 8PT, SIVACON S8, SIVACON S4 and motor control MCC (Motor Control Center) on the basis of SIVACON.


Each unit consists of SIEMENS SIVACON standard removable or retractable modules. A variety of options and configurations of modules, easy installation and convenient replacement of the blocks allow us to implement a continuous power system and collect the equipment for any requirements and needs of the client.

info_icon

The design of the TCU suggests that under the panel Cabinet is low voltage equipment, it can be accessed through doors. Through this organization achieved a high level of safety in the use of electrical networks. Operating conditions it is quite simple: ambient temperature from -5 to +40 degrees Celsius, altitude not exceeding 2000 m above sea level, the lack of combustible gases and conductive objects nearby.

Side of the design panel

Side of the design panel

A uniform system of marking sections and feeders

A uniform system of marking sections and feeders

The positions of the main busbar up to 6300 A

The positions of the main busbar up to 6300 A

The positions of the main busbar, rear up to 7,000 A (top and/or bottom)

The positions of the main busbar, rear up to 7,000 A (top and/or bottom)

The system locks conventional or centralized

The system locks conventional or centralized

Arm door latch

Arm door latch

Download files

download-arrowКаталог SIVACON S8 (pdf, 4061 кб.)

See also

Если таблица не отображается полностью, есть возможность ее двигать проведя пальцем по экрану.

Parameters

Value

Upper operating ambient temperature during operation

up to + 40°С

Lower operating ambient temperature during operation

from + 5°С

High humidity value at 20°C

no more than 90%

Rated operating voltage She)

up to 690 V

Rated insulation voltage (Sh)

1000 V

Horizontal main busbars

Rated current (Position of the busbars at the top) Rated current (Position of the busbars at the back)

up to 6300 A up to 7010 A

Vertical busbars for cabinets with circuit breakers

Rated current

up to 6300 A

Vertical busbars for universal and fixed mounting cabinets

Rated current

up to 1600 A

Vertical busbars for cabinets with PG1VR ZM4 (stationary)

Rated current

up to 1600 A

Vertical busbars for cabinets with PPVR 3#6 (basement)

Rated current

up to 2100 A

Degree of protection 1Р

According to GOST 14254-96. MZK 60529. EY 60529

1Р30.1Р31.1Р40.1Р41.1Р54

Internal division

GOST R 51321.1-2007 MZK 60439-1. part 7.7. ОШ [N 60439-1

Types from 1 to 4b

Overall dimensions

Height

2000:2200 mm

Width

400; 600; 800; 1000:1200:1400 mm

Depth for one-way service

500; 600; 800 mm

Depth for two-sided service

1000:1200 mm

download-arrowОпросный лист (pdf, 358 кб.)

Key features of SIVACON S8

  • Higher reliability thanks to use of components, fully passed the standard tests (tested LVCD)
  • Maximum protection of staff due to security at the occurrence of the arc short circuit and also due to the protection from unauthorized access
  • High quality industrial design to fully integrate with the modern trends in the solution space
  • Efficiency thanks to the small footprint of sections from 400 x 500 mm
  • Service - unilateral, bilateral, or "back to back"
  • The height of the shield at will 2 000 mm, or 2 200 mm
  • Base / plinth 100 mm or 200 mm
  • Efficiency thanks to the use of different methods of installation in one section
  • The flexibility of placing the busbars on the top or rear, 3 - and 4-pole busbar system for currents up to 7,000 A, rated impulse withstand current lpk up to 330 kA
  • Flexible adaptation of the forms of internal separation to individual requirements, the internal division of the TCU by types 1 to 4 (DIN EN 60439-1)
  • Efficiency through the use of universal hinges, allowing you to easily change the position of the doors
  • Economical due to high efficiency ventilation system
  • The flexibility of the connection cable and tires, top, bottom and rear, cable connection from front or rear side
  • Miniature withdrawable units (½ , ¼ ) for motor and cable assemblies up to 63 A

Key features of SIVACON 8PT

  • The tested standard combination of apparatus (TTA)
  • Standardized busbar position at the top of the wardrobe
  • 3 - and 4-pole busbar system for currents up to 7400 A
  • Rated impulse withstand current Ipk up to 375 kA
  • Deep equipment compartment for universal installation
  • Modular structuresand compartment devices
  • Unilateral or bilateral service
  • Cable entry from top or bottom
  • Cable connection from front or rear side

Servismontazhintegratsiya LLC