Menu

Installation of reactive power compensation in low voltage

Adjustable settings for reactive power compensation KRM is designed to maintain a constant given value of power factor (cos φ) in three-phase electrical distribution networks of industrial enterprises and other facilities with voltage up to 690V, frequency 50 Hz.

Installation KRM provide the specified cos φ in the periods of maximum and minimum stresses, and exclude the mode of generation of reactive power.


In networks with a high level of harmonic distortion and the proportion of nonlinear power consumers over 20% of the total load, it is recommended to use a regulated installations, KRMF, which perform the function of improving the power factor, preventing the increase of the harmonic components of voltage and current.

For networks with variable load complement the range of thyristor capacitor Bank type CRMT for systems, static reactive power compensation. This type of equipment is provided with thyristor contactors instead of conventional contactors and is designed for high-speed compensation of loads sensitive to voltage drops.

info_icon

To compensate for the constant (unchanged) reactive power available unregulated install ASO.

Download files

download-arrowКаталог КРМ (pdf, 2669 кб.)

See also

Если таблица не отображается полностью, есть возможность ее двигать проведя пальцем по экрану.

MAIN TECHNICAL CHARACTERISTICS

</tr> width="75">

648

"196">

KRM-0,525-250-25УЗ

"143">

2000x800x600

"143">

2000x800x600

Name

Mr. power, kVAr

Power steps min.

1 nom., And

Dimensions (HxWxD, mm)

Recommended cross section of the supply copper cable, mm2

Weight, kg (no more)

Rated voltage 400 V

KRM-0,4-25-5 UZ

25

5

36

1000x650x300

16

20

KRM-0,4-50-12,5 UZ

50

12,5

72

1000x650x300

35

25

KRM-0,4-75-12,5 UZ

75

12,5

108

1000x650x300

70

35

KRM-0,4-100-25УЗ

100

25

144

2000x800x600

120

130

KRM-0,4-150-25УЗ

150

25

216

2000x800x600

2x70

140

KRM-0,4-200-25УЗ

200

25

288

2000x800x600

2x120

150

KRM-0,4-225-25УЗ

225

25

324

2000x800x600

2x120

150

KRM-0,4-250-25УЗ

250

25

360

2000x800x600

2x150

170

KRM-0,4-275-25УЗ

275

25

396

2000x800x600

2x185

170

KRM-0,4-300-50УЗ

300

50

432

2000x800x600

2x185

180

KRM-0,4-350-50УЗ

350

50

504

2000x800x600

4x95

190

KRM-0,4-400-50УЗ

400

50

576

2000x800x600

4x120

200

KRM-0,4-450-50УЗ

450

50

2000x800x600

4x120

210

KRM-0,4-500-50УЗ

500

50

720

2000x800x600

4x150

220

KRM-0,4-600-50УЗ

600

50

864

2000x800x600

4x185

250

KRM-0,4-800-50УЗ

800

50

1154

2000x1600x600

6x185

400

KRM -0,4-1000-50УЗ

1000

50

1444

2000x1600x600

8x185

420

Rated voltage 440 V

KRM-0,44-100-25УЗ

100

25

132

2000x800x600

120

130

KRM-0,44-125-25УЗ

125

25

165

2000x800x600

2x95

140

KRM-0,44-150-25УЗ

150

25

197

2000x800x600

2x95

155

KRM-0,44-200-25УЗ

200

25

262

2000x800x600

2x120

160

KRM-0,44-225-25УЗ

225

25

295

2000x800x600

2x150

170

KRM-0,44-250-25УЗ

250

25

328

2000x800x600

2x150

175

KRM-0,44-300-50УЗ

300

50

393

2000x800x600

2x185

180

KRM-0,44-325-25УЗ

325

25

426

2000x800x600

2x185

190

KRM-0,44-350-50УЗ

350

50

459

2000x800x600

4x95

200

KRM-0,44-375-50УЗ

375

25

492

2000x800x600

4x120

210

</td>

KRM-0,44-400-50УЗ

400

50

524

2000x800x600

4x120

230

KRM-0,44-500-50УЗ

500

50

656

2000x800x600

4x150

250

Rated voltage 525 V

KRM-0,525-100-25УЗ

100

25

110

2000x800x600

95

130

KRM-0,525-125-25УЗ

125

25

137

2000x800x600

95

140

KRM-0,525-150-25УЗ

150

25

164

2000x800x600

120

155

KRM-0,525-200-25УЗ

200

25

220

2000x800x600

185

160

KRM-0,525-225-25УЗ

225

25

247

2000x800x600

185

170

250

25

275

2000x800x600

2x95

175

KRM-0,525-300-50УЗ

300

50

329

2000x800x600

2x120

180

KRM-0,525-325-25УЗ

325

25

258

2000x800x600

2x120

190

KRM-0,525-350-50УЗ

350

50

385

2000x800x600

2x150

200

KRM-0,525-375-50УЗ

375

25

413

2000x800x600

2x150

210

KRM-0,525-400-50УЗ

400

50

440

2000x800x600

2x185

230

KRM-0,525-500-50УЗ

500

50

550

2000x800x600

4x120

250

Rated voltage 690 V

CUM-0,69-100-25УЗ

100

25

84

2000x800x600

35

130

KRM-0,B9-125-25УЗ

125

25

105

2000x800x600

70

140

KRM-0,69-150-25УЗ

150

25

126

2000x800x600

95

155

KRM-0,B9-200-25УЗ

200

25

167

2000x800x600

150

160

KRM-0,69-225-25УЗ

225

25

188

2000x800x600

185

170

KRM-0,69-250-25УЗ

250

25

209

2000x800x600

185

175

KRM-0,69-300-50УЗ

300

50

251

2000x800x600

2x95

180

KRM-0,69-325-25УЗ

325

25

272

2x120

190

KRM-0,69-350-50УЗ

350

50

293

2000x800x600

2x120

200

KRM-0,69-375-50УЗ

375

25

314

2000x800x600

2x120

210

KRM-0,69-400-50УЗ

400

50

335

2000x800x600

2x150

230

KRM-0,69-500-50УЗ

500

50

418

2000x800x600

2x185

250

Rated voltage 400 V harmonic filters

KRMF-0,4-100-25УЗ

100

25

164

2000x800x600

150

230

KRMF-0,4-150-25УЗ

150

25

246

2000x800x600

2x95

270

KRMF-0,4-200-25УЗ

200

25

328

2x150

320

KRMF-0,4-250-25УЗ

250

25

410

2000x800x600

2x185

370

KRMF-0,4-275-25УЗ

275

25

451

2000x800x600

2x185

385

KRM F-0,4-300-50УЗ

300

50

492

2000x800x600

4x95

420

KRM F-0,4-350-50УЗ

350

50

574

2000x800x600

4x120

460

KRMF-0,4-400-50УЗ

400

50

656

2000x800x600

4x120

520

KRMF-0,4-450-50УЗ

450

50

738

2000x800x600

4x150

560

KRMF-0,4-500-50УЗ

500

50

820

2000x800x600

4x185

630

The installation of the KRM has the following advantages:

  • modular design – allows you to gradually increase the nominal capacity of the installation;
  • accurate control of the values of cos φ (the minimum tier 1 kVAr);
  • the use of specialized contactors with contacts advanced switching and current-limiting resistors, increases the service life of contactors and capacitors;
  • the use of capacitors that have the ability to regenerate itself after the breakdown of the insulating layer;
  • use specialized controllers to automatically control the values of cos φ with protection from harmonic distortion;
  • fuses with high breaking capacity connected to the busbar;
  • small weight and dimension parameters;
  • the possibility of manufacturing plants for the size of the customer.

The use of PFC allows you to:

  • to maintain the required consumer power factor in the automatic mode in the range of 0.8..1 by the connection/disconnection steps of the capacitor banks;
  • to improve the quality of electricity directly in enterprise networks;
  • to reduce the overall energy costs;
  • to reduce the load of the distribution network elements to increase their service life.
  • reducing power losses in cables;
  • the increase in available power on the secondary transformers;
  • the elimination of the voltage drop.

OOO "ServisMontazhIntegratsiya"