Switchgear medium voltage SIMOPRIME licensed by SIEMENS

Switchgear type SIMOPRIME is a factory-assembled device, since the model test according to IEC 62271, VDE 0671-200, GOST 1516.3-96, GOST 14693-90, and is intended for indoor installation. Designed to work in networks with load capacity up to 17.5 kV with short-circuit current up to 40 kA, with a current of busbar up to 3,600 A.


Switchgear type SIMOPRIME is a factory-assembled device, since the model test according to IEC 62271, VDE 0671-200, GOST 1516.3-96, GOST 14693-90, and is intended for indoor installation. Designed to work in networks with load capacity up to 17.5 kV with short-circuit current up to 40 kA, with a current of busbar up to 3600 And

Download files


See also

Если таблица не отображается полностью, есть возможность ее двигать проведя пальцем по экрану.

Parameters

Value

Maximum operating voltage

7.2/12 kV

Rated voltage

6/10 kV

Rated mains frequency

50/60 Hz

One minute power frequency test voltage

32/42 kV

Lightning impulse test voltage (1.2/50 µs)

60/75 kV

Rated current of main circuits

630 A 1000 A 1250 A 2500 A 3600 A

Thermal current (1 and 3 s)

up to 40 kA

Electrodynamic withstand current

up to 100 kA

Internal arc resistance

up to 40 kA

Degree of protection with closed doors according to GOST 14254

up to 1P 5X

Dimensions

Width

600:800 mm

 Depth

1860 mm

Height

2253 mm

Certificates

Declaration of conformity №Р0СС Р11 Д-Р1Ш46.В.00166/19

download-arrowОпросный лист (pdf, 365 кб.)

Advantages and distinctive features

The safety of personnel

  • All switching operations including emergency manual switching is possible only when the closed position, door compartment HV
  • Mechanical interlock between the door of high voltage compartment and switching devices
  • Moving truck circuit breaker is possible only when the closed position, door compartment HV
  • Metal earthed protective curtains and dividing walls partition the class RM
  • Resistance to internal arc up to 40 kA. 3 sec. According to IEC 62271-200, VDE 0671-200, GOST 14693-90 and GOST 1516.3-96
  • The application of vacuum circuit breakers SION and ЗАН5
  • The possibility of maintenance operations without disrupting the normal operation of neighboring cells due to the metal earthed protective curtains and dividing walls
  • Switchgear SIMOPRIME meets the requirements of standards of GOST 14693-90, IEC 62271-200 for the protection of personnel from accidental contact with live and moving parts and protection of equipment against penetration of foreign bodies and splash at the specified design level of protection, namely:
  • the outer metal shell

IP 4X, IP 5X

IP X1, IP X2

  • partitioning into compartments

IP 2X

Reliability

  • Switchgear prefabricated, since the model (standard) tests according to IEC 62271-200
  • Model (standard) test switch, mounted in the cell
  • The use of standard components available worldwide
  • The use of maintenance-free vacuum circuit breakers
  • The quality assurance system certified according to DIN EN ISO 9001
  • Performance, based on international experience
  • Classification LSC2B according to IEC 62271-200 and GOST 14693-90