Menu

Switchgear medium voltage SIMOPRIME licensed by SIEMENS

Switchgear type SIMOPRIME is a factory-assembled device, since the model test according to IEC 62271, VDE 0671-200, GOST 1516.3-96, GOST 14693-90, and is intended for indoor installation. Designed to work in networks with load capacity up to 17.5 kV with short-circuit current up to 40 kA, with a current of busbar up to 3,600 A.


Switchgear type SIMOPRIME is a factory-assembled device, since the model test according to IEC 62271, VDE 0671-200, GOST 1516.3-96, GOST 14693-90, and is intended for indoor installation. Designed to work in networks with load capacity up to 17.5 kV with short-circuit current up to 40 kA, with a current of busbar up to 3600 And

Download files


See also

Если таблица не отображается полностью, есть возможность ее двигать проведя пальцем по экрану.

Settings

Limit

values

Complete switchgear for voltages up to 7.2 kV

Nominal voltage

7.2 kV

Working voltage

6 kV

Nominal frequency

50/60 Hz

The nominal one-minute test voltage of industrial frequency

32 kV

 

Nominal test voltage lightning impulse

60 kV

 

Nominal short-time current, 3s

40 kA

Nominal shock current at 50 Hz

100/104 kA

Rated breaking capacity under short-circuit

40 kA

Nominal current under short-circuit when

50/60 Hz

100/104 kA

 

Nominal operating current team

tires

3600 And

Nominal operating current exhaust

feeders

 

- with the power switch

3600 And

- with vacuum contactor

400 And

 

Settings

Limit

values

Complete switchgeara voltage up to 12 kV

Nominal voltage

12 kV

Working voltage

10 kV

Nominal frequency

50/60 Hz

The nominal one-minute test voltage of industrial frequency

42 kV

 

Nominal test voltage lightning impulse

75 kV

 

Nominal short-time current, 3s

40 kA

Nominal shock current at 50 Hz

100/104 kA

Rated breaking capacity under short-circuit

40 kA

Nominal current under short-circuit when

50/60 Hz

100/104 kA

 

Nominal operating current team

tires

3600 And

Nominal operating current exhaust

feeders

 

- with the power switch

3600 And

- with vacuum contactor

400 And

 

All types of cells

 

Dimensions, mm

Width

In

Cell with the power switch

SION,

630 A - 1000 A

1250 A, 1600 A, 2500 A, 3150 A, 3600 A</p>

Up to 31,5 kA

 

600

800

Up to 40 kA

 

800

800

Cell with vacuum contactor

435/600

435

Cell with breakout breaker busbar

630 A, 1000 A,

1250 A, 2500 A, 3150 A, 3600 A

 

 

600

800

 

 

800

800

The cell sectional disconnector

630 A, 1000 A

1250 A, 1600 A, 2500 A, 3150 A, 3600 A

 

600

800

 

800

800

Cell and module measurement

equipment (TN)

 

600

 

800

Height

H1

The cell with the standard Cabinet

low voltage and IAC 0.1 s

 

2253

 

2253

H2

The cell with the standard Cabinet

low voltage and IAC 1.0 s

 

2425

 

2460

H3

- - -

1780

1780

Depth

T

Standard depth

1860

1860

 

*The depth of a cell with a back channel

for a supply of cable/tyres

top

+400

+400



Advantages and distinctive features

The safety of personnel

  • All switching operations including emergency manual switching is possible only when the closed position, door compartment HV
  • Mechanical interlock between the door of high voltage compartment and switching devices
  • Moving truck circuit breaker is possible only when the closed position, door compartment HV
  • Metal earthed protective curtains and dividing walls partition the class RM
  • Resistance to internal arc up to 40 kA. 3 sec. According to IEC 62271-200, VDE 0671-200, GOST 14693-90 and GOST 1516.3-96
  • The application of vacuum circuit breakers SION and ЗАН5
  • The possibility of maintenance operations without disrupting the normal operation of neighboring cells due to the metal earthed protective curtains and dividing walls
  • Switchgear SIMOPRIME meets the requirements of standards of GOST 14693-90, IEC 62271-200 for the protection of personnel from accidental contact with live and moving parts and protection of equipment against penetration of foreign bodies and splash at the specified design level of protection, namely:
  • the outer metal shell

IP 4X, IP 5X

IP X1, IP X2

  • partitioning into compartments

IP 2X

Reliability

  • Switchgear prefabricated, since the model (standard) tests according to IEC 62271-200
  • Model (standard) test switch, mounted in the cell
  • The use of standard components available worldwide
  • The use of maintenance-free vacuum circuit breakers
  • The quality assurance system certified according to DIN EN ISO 9001
  • Performance, based on international experience
  • Classification LSC2B according to IEC 62271-200 and GOST 14693-90

Servismontazhintegratsiya LLC

All rights reserved, 2020