With advanced personal safety features, an easy-to-use graphical interface and comprehensive built-in motor/load protection, this soft starter is a balanced solution for a wide range of medium voltage applications.
SMI soft starter is delivered as complete cubicle, which reduces the time for installation, commissioning and start up.
See also
Если таблица не отображается полностью, есть возможность ее двигать проведя пальцем по экрану.
Ratings
|
Limits
|
Network Voltage
|
10 kV
|
Rated lighting impulse withstand voltage (1.2/50 microseconds).
|
75kV
|
Power frequency withstand voltage
|
42kV
|
Network frequency
|
50/60 Hz
|
Rated current
|
From 75 to 540 A
|
Thermal current
|
31.5 kA
|
Electrodynamic current
|
81 kA
|
Degree of Protection
|
IP 31
|
Climatic category
|
UHL 3 (УХЛ 3)
|
Access
|
Double-front
|
Internal short-circuit arc classification
|
AFLR
|
Partition class
|
PM
|
Loss of service continuity category
|
LSC1
|
Weight per cubicle
|
1200 kg
|
Dimensions, WxDxH
|
1000х1360х2200 mm
|
Conformity to standards
|
GOST, IEC
|
Power module of Soft Starter
|
MVE (AuCom)
|
MVE Multilingual Controller. ANSI protections
|
48, 66, 37, 51L, 51R, 50, 49/51, 46, 27, 59, 47, 50G, 85, 94/95, 23, 49, 32.
|
- Various start/stop techniques makes it possible to us SMI soft starters in various fields of application.
- Large range of protection functions implemented in the MVE Multilingual Controller provides complete motor protection.
- Ease of use and communication with the MVE Multilingual Controller's multilingual graphic display.
- Motor protection in direct start mode via bypass.
- Possibility to test the soft starter on site with a low voltage motor before connecting the medium voltage motor.
- Real-time graphs clearly illustrate motor operation.
- Detailed event log. 99-entry event log records operation and performance data with timestamps, which facilitates monitoring of motor operation.
- The 8-entry trip log contains trip statuses and operating parameters at time of trip, including the following:
- Phase currents and voltages
- Network frequency
- Soft Starter status
- Time and date
- 100% galvanic isolation. Soft starter control panel is installed in the low voltage compartment of the cubicle. Power section is connected by fibre optic cables through an interface board, eliminating the need for copper wiring and providing complete galvanic isolation of low voltage compartment from the medium voltage power section.